矿山电力变压器与普通电力变压器绝缘纸老化特性对比分析

周一恒 严家明 吴新忠 任子晖

周一恒,严家明,吴新忠,等.矿山电力变压器与普通电力变压器绝缘纸老化特性对比分析[J].工矿自动化,2020,46(11):34 -40..  doi: 10.13272/j.issn.1671 -251x.2020080095
引用本文: 周一恒,严家明,吴新忠,等.矿山电力变压器与普通电力变压器绝缘纸老化特性对比分析[J].工矿自动化,2020,46(11):34 -40..  doi: 10.13272/j.issn.1671 -251x.2020080095
ZHOU Yiheng, YAN Jiaming, WU Xinzhong, et al. Comparison and analysis of aging characteristics of insulation paper between mine power transformer and ordinary power transformer[J]. Industry and Mine Automation, 2020, 46(11): 34-40. doi: 10.13272/j.issn.1671 -251x.2020080095
Citation: ZHOU Yiheng, YAN Jiaming, WU Xinzhong, et al. Comparison and analysis of aging characteristics of insulation paper between mine power transformer and ordinary power transformer[J]. Industry and Mine Automation, 2020, 46(11): 34-40. doi: 10.13272/j.issn.1671 -251x.2020080095

矿山电力变压器与普通电力变压器绝缘纸老化特性对比分析

doi: 10.13272/j.issn.1671 -251x.2020080095
基金项目: 

国家重点研发计划项目(2017YFF0210600)

中国矿业大学“十三五”品牌专业建设自主项目(电子信息工程)

详细信息
  • 中图分类号: TD605

Comparison and analysis of aging characteristics of insulation paper between mine power transformer and ordinary power transformer

  • 摘要: 采集实际寿命周期中矿山电力变压器及普通电力变压器的围屏纸板制作绝缘试品,利用黏度测试仪、扫描电镜测试手段,并根据电力标准,对比分析了矿山电力变压器与普通电力变压器绝缘纸的聚合度、表面形貌等微观结构及局部放电、电气强度等电气性能,探讨了老化过程中微观结构变化对电气性能的影响。分析结果表明:老化过程中绝缘缺陷在绝缘纸中逐渐形成并扩大,相较普通电力变压器绝缘纸,矿山电力变压器绝缘纸的表面形貌变化更加明显,形成的缺陷也更加显著;在老化过程中,普通电力变压器和矿山电力变压器绝缘纸的聚合度均呈现逐渐下降趋势,但矿山电力变压器绝缘纸聚合度的下降速度更快;矿区运行环境是造成矿山电力变压器绝缘纸较普通电力变压器老化严重的主要原因。在运行过程中,矿山电力变压器绝缘纸较普通电力变压器将产生更大的放电量及更多的放电次数,放电相位也更宽;在老化过程中,普通电力变压器和矿山电力变压器绝缘纸的电气强度均呈现逐渐下降趋势,但矿山电力变压器绝缘纸的电气强度低于普通电力变压器;矿山电力变压器绝缘纸微观结构缺陷是导致其电气性能变化更加显著的直接原因。在电力设备状态监测维修过程中,对矿山电力变压器绝缘状态的监测建议从严执行电力标准,电气特征参数更适合用于矿山电力变压器绝缘状态监测及故障诊断。

     